background image

Jaguar Model J-390

7

The combustion air supply must not be susceptible to

contaminants, which may cause corrosion or other

damage to the heat exchanger and components of the

boiler, causing failure of these parts or unsafe operation.
Below is a list of products which must be avoided from

being stored or entering the boiler room or air supply

area:

PRODUCTS TO AVOID

Spray cans containing chloro/fluorocarbons

Permanent wave solutions

Chlorinated waxes/cleaners

Chlorine-based swimming pool chemicals

Calcium chloride used for thawing

Sodium chloride used for water softening

Refrigerant leaks

Paint or varnish removers

Hydrochloric acid/muriatic acid

Cements and glues

Antistatic fabric softeners used in clothes dryers

Chlorine-type bleaches, detergents and cleaning solvents

found in household laundry rooms.

Adhesives used to fasten building products and other

similar products.

ANNUAL SERVICE AND GENERAL MAINTENANCE

A trained and qualified service technician should

perform inspection and general maintenance listed in

Installation and Operating Instructions (Publication

No. J-40) before each heating season and at regular

intervals. 

SAFETY AND OPERATING INSTRUCTIONS

Follow the lighting instructions in this manual. These

instructions are also attached to the boiler. 

SAFETY INFORMATION

For Your Safety Read Before Operating

A. This appliance does not have a pilot. It is equipped

with an ignition device which automatically lights the

burner. Do not try to light the burner by hand.

B. BEFORE OPERATING smell all around the appliance

area for gas. Be sure to smell next to the floor because

some gas is heavier than air and will settle on the floor.

WHAT TO DO IF YOU SMELL GAS:

• Do not try to light any appliance.

• Do not touch any electric switch: do not use any

phone in your building.

• Immediately call your gas supplier from a neighbor’s

phone. Follow the gas supplier’s instructions.

• If you cannot reach your gas supplier, call the fire

department.

C. Use only your hand to turn the gas supply shut off

valve. Never use tools. If the supply shut off will not

turn by hand, don’t try to repair it, call a qualified

service technician. Force or attempted repair may

result in a fire or explosion.

D

DO NOT

use this appliance if any part has been under

water. Immediately call a qualified service technician to

inspect the appliance and to replace any part of the

control system and any gas control which has been

under water.

OPERATING INSTRUCTIONS

1. STOP! Read the safety information above.
2. Set the thermostat to lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition device which

automatically lights the burner. Do not try to light the burner
by hand.

5. Open the gas supply shut off valve, by turning the handle to

be parallel to the gas piping. (See Figure 8).

6. Wait five (5) minutes to clear out any gas, then smell for gas,

including near the floor. If you then smell gas, STOP! Follow
“B” in the safety information above on this page. If you don’t
smell gas, go to next step.

7. Turn on all electric power to the appliance. 
8. Set thermostat to desired setting.

If the appliance will not operate, follow the instructions “To
Turn Off Gas to Appliance” and call your service technician
or gas supplier.

To Turn Off Gas to Appliance

1. Set thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to be

performed.

3. Close the gas supply shut off valve, by turning the handle to

be perpendicular to the gas piping. 
(See Figure 8).

WARNING: If you do not follow these instructions exactly, a
fire or explosion may result causing property damage, 
personal injury or loss of life. 

GAS SUPPLY SHUTOFF VALVE
IN “OPEN” POSITION

GAS SUPPLY SHUTOFF VALVE
IN “CLOSED” POSITION

TURN 90˚
TO CLOSE

TURN 90˚
TO OPEN

Figure 8.

Summary of Contents for J-390

Page 1: ...nity of this or any other appliance __ WHAT TO DO IF YOU SMELL GAS DO NOT try to light any appliance DO NOT touch any electrical switch DO NOT use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas suppli er s instructions If you cannot reach your gas supplier call the fire department __ Installation and service must be performed by a qualified ins...

Page 2: ...s boiler if any part has been underwater Immediately call a qualified service technician to inspect the boiler and to replace any part of the control system and any gas control which has been underwater WARNING Should overheating occur or the gas supply fail to shut off DO NOT turn off or disconnect the electric supply to the circulator pump Instead shut off the gas supply at a location EXTERNAL t...

Page 3: ... Non direct vent installation is shown on Figures 4 5 and 6 1 VENTING AND AIR INTAKE SYSTEM REGULAR INSPECTION Inspect the system regularly for condensation corrosion sagging and or physical damage A qualified professional should service the boiler annually and include such an inspection at that time The homeowner should look over the system monthly for damage water stains any signs of rust other ...

Page 4: ...Jaguar Model J 390 4 AIR INTAKE DO NOT BLOCK 4 DIA VENT PIPE VENT TERMINATION OUTSIDE WALL Figure 4 Non direct vent sidewall venting 102mm 4 DIA VENT PIPE ...

Page 5: ...RMINATION 4 DIA VENT PIPE AIR INTAKE DO NOT BLOCK Figure 6 Non direct vent utilizing an existing chimney as a chase VENT TERMINATION CHIMNEY TOP PLATE 4 DIA VENT PIPE 4 DIA VENT PIPE AIR INTAKE DO NOT BLOCK UNUSED CHIMNEY 102mm 4 DIA VENT PIPE 102mm 4 DIA VENT PIPE 102mm 4 DIA VENT PIPE ...

Page 6: ...ure is normally indicated on the tempera ture display See Figure 1 for location and Figure 9 for digits illustration For most installations it should indicate about 83 to 103 kPa 12 to 15 psi pressure when temperature is about 21 to 38 C 70 to 100 F and from 103 to 172 kPa 15 psi to 25 psi when tem perature is up to 91 C 195 F FOR YOUR SYSTEM there is one correct pressure for each temperature ASK ...

Page 7: ...uilding Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your hand to turn the gas supply shut off valve Never use tools If the supply shut off will not turn by hand don t try to repair it call a qualified service technician Force or attempted repair may result in a fire or ex...

Page 8: ... C 90 to 185 F 2 While d is blinking boiler supply water tempera ture for DHW may be set to desired temperature The setting range is between 40 to 85 C 104 to 185 F 3 While t is blinking DHW tank temperature may be set to desired temperature if tank is equipped with sensor The setting range is between 40 to 85 C 104 to 185 F 4 View actual following temperatures on Temperature Display Press Select ...

Page 9: ...pressed to resume normal operation Error Condition Temperature display indicates the error code Warning Condition Temperature display indicates the error code Jaguar Boiler Display Board Boiler Operation Status Note Blinking dot on Mode Display indicates active heating control burner off Steady dot indicates burner is on Error must be corrected to resume boiler operation Pressing the Reset button ...

Page 10: ...Settable from 40 to 71 C 104 F to 160 F steps of 0 55 C 1 F The default valve is 60 C 140 F Press Enter button to store see note 3 Temperature display shows actual supply water temperature Temperature display shows actual return water temperature Temperature display shows actual DHW tank temperature if the water tank is equipped with sensor Temperature display shows actual flue gas temperature Tem...

Page 11: ...d once the condition returns to normal or is fixed The temperature display shows the error code Pressing the Reset button is not required C WARNING ERRORS Indicated by an H in the mode display Operation of the space heating mode is not affected and the warning is displayed intermittently Operation of the DHW mode is automatically restored once the condition is fixed The temperature display shows t...

Page 12: ... FIN LTD LTEE 6450 Northam Drive Mississauga Ontario L4V 1H9 Phone 905 677 8400 FAX 905 677 1829 Order Desk Fax 905 677 9015 www slantfin ca E mail orderdesk slantfin ca info slantfin ca Slant Fin Corp 2008 ...