background image

Jaguar Model J-390

8

Removing Jacket Front Panel

1.  Turn black screws 1/4 turn to open position.
2. Remove front panel.

To replace the panel, reverse procedure. 

INTEGRATED BOILER CONTROL

The integrated boiler control monitors the status of the

room thermostat, high limit switch, low water cutoff (if

installed), water inlet and outlet sensors, flue gas sensor

and flame sensor. It controls the operation of the circula-

tor, combustion blower, gas valve and spark ignitor. The

boiler control also determines the sequence of operation

and timing for pre and post purge periods, trial for ignition

and lock out. 

The control display board provides information on boiler

operation on a mode and temperature display and can be

viewed, programmed and reset with specific push

buttons. Diagnostic information is also provided on the

display, to help determine the cause of boiler failure. (See

Figure 9).

BOILER CONTROL AND DISPLAY FEATURES

(See Figure 9)
A.

BOILER OPERATION STATUS:

“Mode Display”

shows status of boiler operation. (See Table 1).

B.

VIEW AND CHANGING TEMPERATURES:

Setting

boiler supply water temperature and water tank

temperatures (See Table 2).
Press “Select” button for viewing following different

modes on “Mode Display”
1. While “c” is blinking, boiler supply water tem-

perature for space heating may be set to desired

temperature. The setting range is between 32° to

85°C (90° to 185°F).

2. While “d” is blinking, boiler supply water tempera-

ture for DHW may be set to desired temperature.

The setting range is between 40° to 85°C (104° to

185°F).

3. While “t” is blinking, DHW tank temperature may

be set to desired temperature (if tank is equipped

with sensor). The setting range is between 40° to

85°C (104° to 185°F).

4. View actual following temperatures on

“Temperature Display”, Press “Select” button for

selection:

a. Supply water temperature – Select #1 on

“Mode Display”.

b. Return water temperature – Select #2 on

“Mode Display”.

c. Domestic hot water tank temperature (if tank

equipped with sensor) – Select #3 on “Mode

Display”.

d. Flue gas temperature – Select #4 on “Mode

Display”.

e. Outside temperature (if outside sensor is used)

– Select #5 on “Mode Display”.

C. Display Board Pushbuttons: 

1.

Reset 

- Used to clear a Lockout Error

(indicated with an “A” in the “Mode Display”)

2.

Select 

- Used to scroll through the modes in the

“View and Changing Temperatures” and “Viewing

and Changing System Setting” menus.

3.

Enter

- Used to store values that are changed in

the “View and Changing Temperatures” and

“Viewing and Changing System Setting” menus.

4.

Up 

- Used to increase values in the “View and

Changing Temperatures” and “Viewing and

Changing System Setting” menus.

5.

Down

- Used to decrease values in the “View and

Changing Temperatures” and “Viewing and

Changing System Setting” menus.

"TEMPERATURE" DISPLAY (3 DIGITS)

"UP" PUSH BUTTON

"DOWN" PUSH BUTTON

"ENTER" PUSH BUTTON

"SELECT" PUSH BUTTON

"BURNER STATUS"

STEADY DOT = BURNER ON

BLINKING DOT = BURNER OFF

"MODE" DISPLAY

"RESET"

PUSH BUTTON

Figure 9. Display Board

Summary of Contents for J-390

Page 1: ...nity of this or any other appliance __ WHAT TO DO IF YOU SMELL GAS DO NOT try to light any appliance DO NOT touch any electrical switch DO NOT use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas suppli er s instructions If you cannot reach your gas supplier call the fire department __ Installation and service must be performed by a qualified ins...

Page 2: ...s boiler if any part has been underwater Immediately call a qualified service technician to inspect the boiler and to replace any part of the control system and any gas control which has been underwater WARNING Should overheating occur or the gas supply fail to shut off DO NOT turn off or disconnect the electric supply to the circulator pump Instead shut off the gas supply at a location EXTERNAL t...

Page 3: ... Non direct vent installation is shown on Figures 4 5 and 6 1 VENTING AND AIR INTAKE SYSTEM REGULAR INSPECTION Inspect the system regularly for condensation corrosion sagging and or physical damage A qualified professional should service the boiler annually and include such an inspection at that time The homeowner should look over the system monthly for damage water stains any signs of rust other ...

Page 4: ...Jaguar Model J 390 4 AIR INTAKE DO NOT BLOCK 4 DIA VENT PIPE VENT TERMINATION OUTSIDE WALL Figure 4 Non direct vent sidewall venting 102mm 4 DIA VENT PIPE ...

Page 5: ...RMINATION 4 DIA VENT PIPE AIR INTAKE DO NOT BLOCK Figure 6 Non direct vent utilizing an existing chimney as a chase VENT TERMINATION CHIMNEY TOP PLATE 4 DIA VENT PIPE 4 DIA VENT PIPE AIR INTAKE DO NOT BLOCK UNUSED CHIMNEY 102mm 4 DIA VENT PIPE 102mm 4 DIA VENT PIPE 102mm 4 DIA VENT PIPE ...

Page 6: ...ure is normally indicated on the tempera ture display See Figure 1 for location and Figure 9 for digits illustration For most installations it should indicate about 83 to 103 kPa 12 to 15 psi pressure when temperature is about 21 to 38 C 70 to 100 F and from 103 to 172 kPa 15 psi to 25 psi when tem perature is up to 91 C 195 F FOR YOUR SYSTEM there is one correct pressure for each temperature ASK ...

Page 7: ...uilding Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your hand to turn the gas supply shut off valve Never use tools If the supply shut off will not turn by hand don t try to repair it call a qualified service technician Force or attempted repair may result in a fire or ex...

Page 8: ... C 90 to 185 F 2 While d is blinking boiler supply water tempera ture for DHW may be set to desired temperature The setting range is between 40 to 85 C 104 to 185 F 3 While t is blinking DHW tank temperature may be set to desired temperature if tank is equipped with sensor The setting range is between 40 to 85 C 104 to 185 F 4 View actual following temperatures on Temperature Display Press Select ...

Page 9: ...pressed to resume normal operation Error Condition Temperature display indicates the error code Warning Condition Temperature display indicates the error code Jaguar Boiler Display Board Boiler Operation Status Note Blinking dot on Mode Display indicates active heating control burner off Steady dot indicates burner is on Error must be corrected to resume boiler operation Pressing the Reset button ...

Page 10: ...Settable from 40 to 71 C 104 F to 160 F steps of 0 55 C 1 F The default valve is 60 C 140 F Press Enter button to store see note 3 Temperature display shows actual supply water temperature Temperature display shows actual return water temperature Temperature display shows actual DHW tank temperature if the water tank is equipped with sensor Temperature display shows actual flue gas temperature Tem...

Page 11: ...d once the condition returns to normal or is fixed The temperature display shows the error code Pressing the Reset button is not required C WARNING ERRORS Indicated by an H in the mode display Operation of the space heating mode is not affected and the warning is displayed intermittently Operation of the DHW mode is automatically restored once the condition is fixed The temperature display shows t...

Page 12: ... FIN LTD LTEE 6450 Northam Drive Mississauga Ontario L4V 1H9 Phone 905 677 8400 FAX 905 677 1829 Order Desk Fax 905 677 9015 www slantfin ca E mail orderdesk slantfin ca info slantfin ca Slant Fin Corp 2008 ...

Reviews: