Temperature compensation
A battery voltage compensation system maintains the charge characteristics within the limits specified by the
battery manufacturer across the whole of the operational temperature range.
cover tamper switch / wall removal tamper detection
A switch fitted with a wire loop detects cover opening and wall removal on the 12 V and 24 V versions
(no "wall removal" detection on C6/C7).
The customer is responsible for cabling the switches ("cover open" and "wall removal") in series. During the
installation one screw come to press on a snap contact (C38 version) or on a swiveling snap contact (C24
version) intended to warn of the arrachement wall. This screw is selling with the versions C24
Monitoring of battery current:
The charge current is adapted to the nominal capacity of the batteries and is electronically monitored
and limited to the values prescribed by the manufacturer. configuration Jumper on additional card,
configuration 25%, 50% 75% ( manufactury configuration at 75% for AES application)
GLOSSAR
Netzfehler:
Liegt Spannung am Gerät an, wird dies durch die LED Anzeige am Gerät angezeigt.
Leuchtet die LED nicht, ist keine Netzspannung vorhanden
Ladefehler:
Störung des Ladevorgangs
Anzeige des ordnungsgemäßen Betriebs durch LED.
Ausganganzeige:
Anzeige Ausgangsspannung durch grüne LED an allen Verbraucherausgängen. Wenn an einem der Ausgänge
keine Spannung anliegt, erlischt die LED.
Batteriefehler:
- Ein Batteriefehler liegt vor, wenn die Batterie nicht vorhanden ist oder die Spannung kleiner ist als die
Schwellenspannung die das Gerät benötigt.
Im Batteriebetrieb:
-
Anzeige einer Spannung kleiner als 1,85V/Zelle über eine orangefarbene, blinkende LED
Potenzialfreie Kontakte
- Fernmeldung über isolierte NO/NC Kontakte (positive Sicherheit, 1A @ 24Vdc, 0.5A @ 120Vac).