English - Installation manual 

 

You have just acquired an 

AXS2

 uninterruptible power unit by SLAT, and we thank you for your choice. 

In this manual, you will find all the instructions you need to install it. 
For proper functioning of the unit, we recommend that these instructions be followed very carefully.  
 

Safety precautions 

 
AXS2 is an emergency power supply designed to be connected to the public distribution 230V network. It 
ensures continuity of service for equipment in case of power failure. You can find more information in the 
datasheet for download on our website www.slat.com 

 

To avoid any risk of electric shock, all 

INTERVENTIONS

 must be carried out with the equipment 

SWITCHED OFF

 (upstream two-pole circuit-breaker open).  

 

Interventions with the equipment switched on are authorized only when it is impossible to switch the 

equipment off. The operation must only be performed by qualified personnel. 

 

During installation, connect the ground wire first and disconnect it last when dismantling. 

 

Mount the appliance in a vertical position. 

 

Provide sufficient convection (top / bottom clearance minimum 30mm) 

 

Size and protect cables defined according to the maximum current input / output (>0.2mm²/A). 

 

Observe the thermal and mechanical limits. 

 

The battery is maintenance-free. Do not open it. 

 

Attention, there is a blast hazard if the battery is replaced with a wrong battery type! 

 

Scrap the used batteries according to the directives 

 

Indoor use only 

 

Clean the cabinet with a soft rag. 

 

Environment and public health protection standards and directives 

  

Complies with EN 60950 -1 SELV class; EN 61000-6-1; EN 61000-6-2; EN 61000-6-3; EN 61000-6-4; 
55022 + A1 Class B; EN 50131-6 Grade 2 for versions of the appliance in cabinets with a wall removal 
contact and cover opening.  
  
At the end of life, the product must be recycled. SLAT recycles its products at end of life. 
 

Associated batteries  

-

 

recombination-type lead, capacity depending on charger ratings:  1.2Ah; 2.1Ah; 7Ah; 12Ah; 17Ah; 24Ah; 
40Ah 

-

 

floating recharge at C/10 

-

 

the battery jumper cables are fitted with connectors according to each associated battery  

Environmental specifications 

operating temperature: - 5°C to 50°C

 

storage temperature: - 25 to + 85°C

 

operating relative humidity: 20 to 95%

 

Electrical input specifications  

-

 

single-phase voltage:  230V (195V-264V) 

-

 

frequency: 50-60Hz (from 45 to 65Hz) 

-

 

neutral systems: TT, TN, IT 

-

 

a D curve circuit breaker with easy access to be provided upstream 

-

 

primary current @230V: 

0.25A

 (12V 2A - 24V 1A); 

0.75A

 (12V 5A - 24V 2.5A); 

1A

 (12V 10A - 24V 5A) 

Electrical output specifications  

-

 

"floating" load output in relation to the ground. 

-

 

float voltage: 

13.6V

 (12V 2A - 12V 5A - 12V 10A); 

27.2V

 (24V 1A - 24V 2.5A 

– 24V 5A) 

-

 

current limitation: 

1A

 (24V 1A); 

2A

 (12V 2A); 

2.5A

 (24V 2.5A); 

5A

 (12V 5A 

– 24V 5A); 

10A

 (12V 10A) 

Alarm reports 

-

 

2 dry contacts (open when faulty) 1A@24Vdc, 0.5A@120Vac  : 

o

 

mains fault or rectifier fault 

o

 

battery low voltage fault 

-

 

Indicated by a LED on the front panel 

Summary of Contents for AXS2 12V 2A

Page 1: ...olaire amont ouvert Les travaux sous tension ne sont autoris s que pour les exploitations o la mise hors tension est impossible L intervention doit tre r alis e uniquement par du personnel habilit Lor...

Page 2: ...uvert en d faut 1A 24Vdc 0 5A 120Vac o d faut secteur ou d faut redresseur o d faut tension de batterie basse signalisation par led en fa ade Protection fusibles sur carte lectronique voir tableau Ins...

Page 3: ...th a wrong battery type Scrap the used batteries according to the directives Indoor use only Clean the cabinet with a soft rag Environment and public health protection standards and directives Complie...

Page 4: ...romversorgungsnetz vorgesehen ist Sie stellt die ununterbrochene Betriebsbereitschaft der Anlagen im Falle eines Stromausfalls sicher Weitere Informationen und Einzelheiten finden Sie im Datasheet das...

Page 5: ...orts 2 potentialfreie Kontakte ge ffnet bei Fehler 1A 24Vdc 0 5A 120Vac o Fehler Netz oder Fehler Gleichrichter o Fehler Batteriespannung niedrig Meldung durch LED an der Vorderseite Schutzeinrichtung...

Page 6: ...den Let op er is een risico van explosiegevaar als de batterij wordt vervangen door een verkeerd type Verwijder gebruikte batterijen volgens de instructies Alleen voor intern gebruik Reinig met een za...

Page 7: ...uik batterij alarmoverdragers o 0 2 2 5 mm 12V 2A 12V 5A 24V 1A 24V 2 5A o 0 2 6 mm 12V 10A 24V 5A te strippen lengte 7 mm bare delen kabel sectoren moet worden geplooid voordat ze aangesloten op de k...

Page 8: ...C F2 5x20 1A aM 250V HPC 24V 2 5A F1 5x20 2A aM 250V HPC F2 5x20 2 5A aM 250V HPC 24V 5A F1 5x20 2A aM 250V HPC Resettable Fuse F7 F8 5x20 6 3A aM 250V HPC SLAT 11 rue Jean Elys e Dupuy BP66 69543 Cha...

Reviews: