1. General information
1.1.
Environmental specifications
Operating temperature:
-10 °C to +45 °C at 100 % charge.
-10 °C to +55 °C at 75 % charge.
Storage temperature: -25 to +85 °C.
Relative humidity: 20 to 95 %.
1.2.
Electrical input and output specifications
1.2.1
Network input
-
single-phase voltage: 195 V to 264 V.
-
frequency: 47 to 63 Hz.
-
class I.
-
neutral systems: TT, TN, IT.
-
Primary current @ 195 V: 1 A.
-
circuit breaker (D curve) to be provided upstream.
1.2.2
Output
-
Rated voltage: 24 V.
-
Floating voltage set at half-load and at 25 °C: 27.2 V
±0.5 %.
-
2 ‘amplifiers’ outputs with a current of 20A maximum per output.
-
3 ‘controllers’ outputs with a current of 5A maximum per output.
-
the maximum current for all the outputs is 40A.
-
the power supply can function without load current: Imin = 0 A.
1.2.3
Specific features and technical specifications
The power supply and the public address and voice alarm system (PA/VA) must be powered by the same mains.
In normal operating mode
: The power supply equipment recharges then maintains on charge from the normal backup
supply, and provides current to PA/VA not exceeding Imax a.
In emergency operating mode
: the total operating current is provided by the battery, including the current of the PA/VA
amplifiers not exceeding ‘Imax b mains not present’ (
≤
40A) depending on the size of the battery.
Imax b = 40 A (mains not present).
Imax b = 6 A (mains present).
Imax a = 6 A – C/20 (battery capacity).
1.2.4
Autonomy
To determine the autonomy of your power supply and interpret the battery code dates, consult our website:
1.2.5. Authorized battery capacities
The power supply can be coupled with 24 to 110 Ah batteries.