Fuse protections
F1 mother board (mains): rating
breaking capacity – size
2 A Time lag
5x20
1500 A
F1 to F2 ‘amplifiers board’ (2 outputs) :
rating - type – size
20 A gG
10x38
F1 to F3 ‘controlers’ board (3 outputs):
rating - type – size
5A F
5x20
8.
Troubleshooting procedure
If the power supply does not deliver voltage
•
Check mains presence on the mains terminal strip
•
Check the fuses
•
Check the voltage value on output terminals
•
The voltage on the battery cables must be identical to that of the load
•
Check that each 12 Vdc battery has a voltage greater than or equal to 11.5 Vdc
•
Repeat the measurement after having disconnected the load and the battery
•
Recheck the signalling of the indicator lights (see chapter 5)
•
If all the steps are validated, check the compatibility of your load
If the battery indicator light remains red
•
Check if the battery voltage is between 12Vdc and 30Vdc
•
Check the battery voltage polarity
If the battery does not take over after a mains fault
•
Check the voltage on the battery terminals
•
Check the battery fuse
•
Check the voltage on output terminals
If the indicator lights are not illuminated
•
Check mains presence on the mains terminal strip
•
Check the battery connection
•
Check that the wire ribbon is properly connected
•
Check the voltage on output terminals
For additional technical assistance, contact the SLAT hotline
+ 33 (0) 4 78 66 63 70
For return requests, visit our website
http://www.slat.fr/formulaireRMA.php
or contact SLAT After-Sales Service to obtain an RMA (Return Material Authorisation) number.
Returns are not accepted without an RMA number.