7.9.2
Reconnecting the AC Side
1. Reconnect the supply voltage and external voltages (see Section 7.9.1, page 103).
2. Reconnect the AC voltage of the MV transformer (see Section 7.8, page 102).
3. Switch on the AC disconnection unit in the inverter.
7.9.3
Reconnecting the DC Side
1. Insert all fuses and disconnection blades into all fuse holders of the inverter. Use an LV/HRC fuse extractor.
2. Screw on the protective covers over the fuses (torque: 5 Nm).
3. Switch on the DC voltage in the DC main distribution or DC subdistribution (see documentation of the main or
subdistribution).
7.9.4
Restarting the Inverter
• Turn the key switch to
Start
.
7.10
Reconnecting the Supply Voltage of the Station Subdistribution
1. In case the transformer for internal power supply has been disconnected, switch on the transformer protective
device.
2. Switch on the main switch of the supply voltage
Voltage Supply Power Outlet
.
3. Switch on the circuit breakers of the inverters
Voltage Supply SC1
and
Voltage Supply SC2
.
4. Switch on the circuit breaker of the Communit and lighting
Voltage Supply Lighting/Communit
.
5. Switch on the circuit breaker of the optional fans
Fan
.
6. Switch on the circuit breaker of the outlet
Socket
.
7. Switch on any additional supply voltages.
7 Disconnecting and Reconnecting
SMA Solar Technology AG