2. Screw the left-hand ventilation grid on (torque: 20 Nm,-head
size T40).
3. Insert the right-hand ventilation grid.
4. Screw the right-hand ventilation grid on (torque: 20 Nm,-head
size T40).
12.3.2 Mounting and Disassembly Work in the Medium-Voltage Switchgear
12.3.2.1 Disassembling and Mounting the Kick Plates
Disassembling the kick plate
1. Loosen all screws of the kick plate.
2. Carefully pull the kick plate forwards by 80 mm to 100 mm.
3. Loosen the grounding strap from the kick plate.
4. Remove the kick plate.
Mounting the kick plate
1. Position the kick plate.
2. Tighten the grounding strap on the panel (torque: 14 Nm).
3. Check that the grounding strap is securely attached.
4. Attach the kick plate with the previously removed screws.
12 Periodic Actions