12.4
Cable Entry
12.4.1 Inserting the Cables through the Base Plates
12.4.1.1 Overview of the Base Plates on the MV Power Station
The MV Power Station is fitted with base plates through which the cables are inserted. The cables should be protected
between the foundation and the MV Power Station. Cable protection measures are customer responsibility.
Figure 52: Position of the base plates and openings for cables
Position
Designation
A
Base plate of the Sunny Central in the MV Power Station 1000SC-JP / 1250SC-JP /
1600SC-JP
B
Base plate of the Sunny Central in the MV Power Station 500SC-JP / 630SC-JP / 800SC-JP
C
Base plate of the medium-voltage switchgear:
• 6 openings for single-core cables; maximum cable diameter: 55 mm
D
Base plate with cable glands for the data cables and grounding cables:
• 3 x PG9 for cable diameters from 6 mm to 8 mm
• 3 x PG11 for cable diameters from 8 mm to 10.5 mm
• 4 x PG16 for cable diameters from 13 mm to 16 mm
• 4 x PG21 for cable diameters from 17 mm to 20 mm
12.4.1.2 Inserting Cables through the Base Plates of the Inverters
Requirement:
☐ The service platform in front of the inverter compartment must be installed.
Procedure:
1. Open the inverter compartment (see Section 12.1, page 159).
2. Cut the cables to the required length. Allow for some reserve.
12 Periodic Actions
SMA Solar Technology AG
System Manual
167
MVPS22JP-SH-en-11