14.1.4.2 Status Values
Name
Values
Description
Mode
---
Initialization
Waiting
Zone Monitoring is activated, but the minimum current for
the evaluation is not yet reached.
Operation
Zone Monitoring is activated and the minimum current for
the evaluation is reached.
Disturbance
Disturbance
Error
Error
Error
---
There is no warning, disturbance or error to display.
ConfigFail
Current inputs are not configured. At least two inputs
have to be configured.
ZoneValueLow
At least one input has an input current which is too low.
ZoneValueFail
For at least one input, the input current is no longer mea-
sured (input current ≤ 2 A)
CalibrationFail
Calibration has failed.
DevNotReachable
I/O module has not answered for at least 30 seconds.
StatusZone[x]
---
No error
ZoneValueLow
The input has an input current which is too low.
ZoneValueFail
For the input, the input current is no longer measured (in-
put current ≤ 2 A).
14.2
Parameters
14.2.1 Inverter
14.2.1.1 Power Limitation
Name
Description
Value/range
Explanation
Default
value
Plimit*
Limitation of the nominal
device power including
apparent power
0 kW to 500 kW
Sunny Central 500CP-JP
500 kW
0 kW to 700 kW
Sunny Central 630CP-JP
700 kW
0 kW to 880 kW
Sunny Central 800CP-JP
880 kW
Pmax**
Limitation of the nominal
power
0 kW to 500 kW
Sunny Central 500CP-JP
500 kW
0 kW to 700 kW
Sunny Central 630CP-JP
700 kW
0 kW to 880 kW
Sunny Central 800CP-JP
880 kW
14 Operating Data and Parameters
SMA Solar Technology AG
System Manual
MVPS22JP-SH-en-11
220