14.2.1.4 Insulation monitoring
Name
Description
Value/range
Explanation
Default
value
IsoErrIgn*
Ignore insulation error
Off
Deactivated
Off
On
Activated
Run
Error is only ignored when the in-
verter is in feed-in operation.
RemMntSvc
PV array grounding is
deactivated.
Off
Deactivated
Off
On
Activated
RisoCtlWarn
Warning threshold for
the insulation monitoring
device iso-PV1685
0 kΩ to 50 kΩ
‒
45 kΩ
PvVtgRisoStart
Start voltage of insulation
measurement
0 V to 1,200 V
Sunny Central 500CP-JP
410 V
Sunny Central 630CP-JP
610 V
Sunny Central 800CP-JP
760 V
PvVtgRisoDif
Differential voltage to
PvVtgStrLevMin
for
switching from insulation
measurement to feed-in
operation
−250 V to +250 V
‒
0 V
IsoDev*
Selection of insulation
monitoring device
isoPV3
‒
isoPV3
isoPV1685
‒
* To view or change this parameter, you must enter the installer password.
14.2.1.5 Project-Specific Parameters
Name
Description
Value/range
Explanation
Default
value
PvPwrMinTr
Threshold for starting the
MPP tracker
0 kW to 20 kW
‒
20 kW
PvPwrMinTrT
Timeout for starting the
MPP tracker
1 s to 1,800 s
‒
600 s
PvVtgStrLevMin
*
Threshold for switching
to feed-in operation
0 V to 1,200 V
Sunny Central 500CP-JP
410 V
0 V to 1,200 V
Sunny Central 630CP-JP
610 V
0 V to 1,200 V
Sunny Central 800CP-JP
760 V
14 Operating Data and Parameters
SMA Solar Technology AG
System Manual
233
MVPS22JP-SH-en-11