Name
Description
Value/range
Explanation
Default
value
Surge Arrester1
*
Alarm contact (e.g. theft protec-
tion for Sunny String-Monitor)
Activ High
Contact activated when volt-
age is present
0
Activ Low
Contact activated when no
voltage is present
Deactivated
Contact deactivated
Surge Arrester2
*
Alarm contact
Activ High
Contact activated when volt-
age is present
0
Activ Low
Contact activated when no
voltage is present
Deactivated
Contact deactivated
* To change these parameters, you must enter the installer password.
** These parameters are only visible after entering the installer password.
14.2.4 Zone Monitoring
Name
Description
Value/range
Explanation
Default
value
DcCfg.AmpMax[1]
Maximum current of
input 1
0 A to 500 A
‒
0 A
DcCfg.AmpMax[2]
Maximum current of
input 2
0 A to 500 A
‒
0 A
DcCfg.AmpMax[3]
Maximum current of
input 3
0 A to 500 A
‒
0 A
DcCfg.AmpMax[4]
Maximum current of
input 4
0 A to 500 A
‒
0 A
DcCfg.AmpMax[5]
Maximum current of
input 5
0 A to 500 A
‒
0 A
DcCfg.AmpMax[6]
Maximum current of
input 6
0 A to 500 A
‒
0 A
DcCfg.AmpMax[7]
Maximum current of
input 7
0 A to 500 A
‒
0 A
DcCfg.AmpMax[8]
Maximum current of
input 8
0 A to 500 A
‒
0 A
MaxTol
Tolerance in percent
by which the input
current may deviate
from the mean value
0.1 % … 100 %
‒
4.0 %
14 Operating Data and Parameters
SMA Solar Technology AG
System Manual
239
MVPS22JP-SH-en-11