General Data
Operating temperature range
−25°C to +40°C / −25°C to +55°C*
Self-consumption in operation**
< 3800 W
Standby consumption***
< 200 W + 950 W
Internal auxiliary supply voltage
230 V / 400 V (3/N/PE), 50 Hz / 60 Hz
Maximum permissible value for relative humidity (non-
condensing)
15% to 95%
Maximum operating altitude above mean sea level
1000 m
Maximum operating altitude above MSL for option "In-
stallation at high altitudes"
1001 m to 2000 m / 2001 m to 3000 m
Fresh air consumption**
6000 m
3
/h
Degree of protection of medium-voltage compartment as
per IEC 60529
IP23D
Degree of protection of transformer compartment and in-
verter compartment as per IEC 60529
IP00
* optional
** information based on inverter
*** separated according to consumption of the inverter and standby power losses of the transformer
15.6
MV Power Station 1600SC-JP
DC Input
MPP voltage range at +25°C
641 V to 850 V
MPP voltage range at +50°C
583 V to 850 V
Maximum input current
2 x 1400 A
Number of independent MPP inputs
2
Number of DC inputs
18
AC Output
AC power at +25°C*
1760 kVA
AC power at +40°C*
1664 kVA
AC power at +50°C*
1600 kVA
Nominal AC voltage
20 kV
Optional nominal voltages
10 kV to 13 kV
AC power frequency
50 Hz / 60 Hz
Maximum total harmonic distortion
< 3 %
Maximum output current at 20 kV
51 A
15 Technical Data
SMA Solar Technology AG
System Manual
247
MVPS22JP-SH-en-11
Summary of Contents for 1000-1SC