Error no. Explanation
Inverter behavior
Corrective measures
S1
S2
R
8702
Several digital active power set-
points are available.
W
W
‒
• Contact Service partner.
8703
Power factor of the external reac-
tive power setpoint is invalid.
W
W
‒
• Contact Service partner.
8704
External active and reactive power
setpoints are invalid.
W
W
‒
• Contact Service partner.
9000
Power electronics self-test is run-
ning. This message disappears
once the self-test is complete.
W
W
‒
‒
9008
Doors have been opened during
operation.
30 s
1 min
‒
• Contact Service partner.
9009
Fast stop has tripped.
30 s
30 s
‒
• Eliminate error and switch fast stop back
on.
9013
This relates to a grid management
shutdown. The error is reset by a
signal from the grid operator or
from the safety system of the grid
interconnection point.
30 s
30 s
‒
• Eliminate error and switch fast stop back
on.
9019
Defective fast stop
30 s
C
‒
• Check the fast stop cabling.
9.3.4.6
Displaying Disturbance Messages for Active Power Limitation
The instantaneous value
P‑WModFailStt
displays errors or warnings associated with active power limitation.
Procedure:
1. Log into the user interface (see Section 12.8.1, page 177).
2. Select the instantaneous value
P-WModFailStt
.
Display
Cause and corrective measures
Off
No mode for active power limitation has been selected.
OK
A mode for active power limitation has been selected and no error is present.
ComFail
The mode
WCtlCom
has been selected and the expected signal with a valid active
power limitation has been absent for at least five minutes.
Corrective measures:
• Ensure that the communication units can be accessed via the Internet.
• Ensure that the communication units are connected correctly.
• Ensure that the cabling between the communication units is ok.