Danger to life from electric shock when entering the PV field
Ground-fault monitoring does not provide protection from personal injury. PV modules which are grounded with
ground-fault monitoring discharge voltage to ground. Entering the PV field can result in lethal electric shocks.
• Ensure that the insulation resistance of the PV field exceeds the minimum value. The minimum value of the
insulation resistance is: 1 kΩ.
• Before entering the PV field, switch the PV modules to insulated operation.
• Configure the PV power plant as a closed electrical operating area.
Danger to life due to arc fault caused by fault in the medium-voltage switchgear
If there is a fault in the medium-voltage switchgear, arc faults may occur during operation of the product which can
result in death or serious injuries. If arc faults occur in the medium-voltage switchgear, the pressure evacuates under
the compartment of the medium-voltage switchgear.
• Only perform work on the medium-voltage switchgear when it is in a voltage-free state.
• Only perform switching operations on the medium-voltage switchgear from the service platform.
• Do not touch or access the roof of the medium-voltage switchgear when medium voltage is connected.
• When switching operations are performed, all persons that are not on the service platform have to keep a safe
distance from the product.
• All work and switching operations on the medium-voltage switchgear must only be performed by qualified
persons wearing adequate personal protective equipment.
Risk of burns due to hot components
Some components of the product can get very hot during operation. Touching these components can cause burns.
• Observe the warnings on all components.
• During operation, do not touch any components marked with such warnings.
• After switching off the product, wait until any hot components have cooled down sufficiently.
• Wear suitable personal protective equipment for all work on the product.
Danger of falling from service platforms
Icy, moist or sand-covered service platforms may be slippery. Service personnel can be injured by slipping or falling
from service platforms.
• Wear suitable personal protective equipment for all work on the product.
• Before stepping onto the service platform, ensure that there is no layer of snow, ice, sand or moisture on the
platform.
• Do not keep any objects near or on the service platforms.
2 Safety
SMA Solar Technology AG
System Manual
17
MVPS22JP-SH-en-11
Summary of Contents for 1000-1SC
Page 257: ......