Status messages of the reactive power setpoint
Name
Display
Description
Q-VArModStt
Off
No mode for specifying the reactive power setpoint has been se-
lected.
VdcMax
The reactive power is limited due to DC voltage being too high.
VacLimMax
The reactive power is limited due to AC voltage being too high.
VacLimMin
The reactive power is limited due to the AC voltage being too low.
SMaxVdcHigh
The maximum apparent power value is reduced. If the maximum DC
voltage increases, the reactive power is reduced.
SMax
The reactive power is limited by the maximum apparent power.
Tmp
The reactive power is limited by temperature derating.
AmpAC
The reactive power is limited via an AC current limitation.
P
The reactive power is limited due to the priority of the active power
setpoint.
FrtLim
The reactive power is limited due to the FRT voltage limit.
Displacement power factor and power setpoint
Name
Display
Description
PF
−
Current displacement power factor cos φ
PFExt
OvExt
Overexcited
UnExt
Underexcited
P-WSpt
−
Current power specification
14.1.1.2 Error Channels
Name
Description
Prio
Priority of error message
Msg
Error message
Dsc
Measure for error correction
TmsRmg
Time until reconnection
GriSwStt
Status of the AC contactor
Mode
Operating state of the inverter
Error
Localization of the error
ErrNo
Error number
ErrNoFirst
Error number of the first error
14 Operating Data and Parameters
SMA Solar Technology AG
System Manual
MVPS22JP-SH-en-11
216
Summary of Contents for 1000-1SC
Page 257: ......