Name
Description
Value/range
Explanation
Default
value
Qmax**
Limitation of reactive
power
0 kVAr to 220 kVAr
Sunny Central 500CP-JP
220 kVAr
0 kVAr to 310 kVAr
Sunny Central 630CP-JP
310 kVAr
0 kVAr to 385 kVAr
Sunny Central 800CP-JP
385 kVAr
QEnsure**
Guaranteed reactive
power
0 kVAr to 500 kVAr
Sunny Central 500CP-JP
0 kVAr
0 kVAr to 700 kVAr
Sunny Central 630CP-JP
0 kVAr
0 kVAr to 880 kVAr
Sunny Central 800CP-JP
0 kVAr
QoDQmax*
Limitation of reactive
power in the operating
state "Q at Night".
The reactive power can-
not exceed
Qlimit
.
0 kVAr to 500 kVAr
Sunny Central 500CP-JP
150 kVAr
0 kVAr to 700 kVAr
Sunny Central 630CP-JP
210 kVAr
0 kVAr to 880 kVAr
Sunny Central 800CP-JP
264 kVAr
PFAbsMin*
Limitation of the displace-
ment power factor cos φ
0.5 to 1
The parameter should not fall be-
low 0.8 in normal operation.
0.9