Name
Description
Range
Explanation
Default value
VCtllLimTm
Delay time for undervolt-
age level 1
0 ms -
to 1,000,000 ms
‒
1,000 ms
VCtlllLim
Threshold for undervolt-
age release level 2
0% to 100%
‒
45%
VCtlllLimTm
Delay time for undervolt-
age level 2
0 ms -
to 1,000,000 ms
‒
300 ms
VCtlMin
Threshold for undervolt-
age release level 3
0% to 100%
‒
0
VCtlMinTm
Delay time for undervolt-
age level 3
0 ms -
to 1,000,000 ms
‒
1,000,000 ms
VCtllCharEna
Activation of dynamic un-
dervoltage detection
Off
Deactivated
Off
On
Activated
VCtllCharTm
Start time of dynamic un-
dervoltage detection
0 ms to
1,000,000 ms
‒
77 ms
VCtlOpMinNo
m
Minimum connection
voltage
0% to 100%
‒
90%
VCtlOpMaxNo
m
Maximum connection
voltage
100% to 200%
‒
110%
HzCtlOpMin
Minimum connection fre-
quency
45 Hz to 50 Hz
For 50 Hz grid
49.5 Hz
55 Hz to 60 Hz
For 60 Hz grid
59.4 Hz
HzCtlOpMax
Maximum connection fre-
quency
50 Hz to 55 Hz
For 50 Hz grid
50.5 Hz
60 Hz to 65 Hz
For 60 Hz grid
60.6 Hz
HzCtlOpMaxR
econ
Maximum connection fre-
quency after grid error
50 Hz to 55 Hz
For 50 Hz grid
50.5 Hz
60 Hz to 65 Hz
For 60 Hz grid
60.6 Hz
HzCtlMax
Threshold for overfre-
quency level 3
50 Hz to 55 Hz
For 50 Hz grid
0
60 Hz to 66 Hz
For 60 Hz grid
HzCtlMaxTm
Delay time for overfre-
quency level 3
0 ms -
to 1,000,000 ms
‒
1,000,000 ms
HzCtlhhLim
Threshold for overfre-
quency level 2
50 Hz to 55 Hz
For 50 Hz grid
52 Hz
60 Hz to 66 Hz
For 60 Hz grid
62 Hz
HzCtlhhLimTm
Delay time for overfre-
quency level 2
0 ms -
to 1,000,000 ms
‒
600 ms
HzCtlhLim
Threshold for overfre-
quency level 1
50 Hz to 55 Hz
For 50 Hz grid
51 Hz
60 Hz to 66 Hz
For 60 Hz grid
61.2 Hz
HzCtlhLimTm
Delay time for overfre-
quency level 1
0 ms -
to 1,000,000 ms
‒
1,000 ms
14 Operating Data and Parameters
SMA Solar Technology AG
System Manual
MVPS22JP-SH-en-11
230