Name
Description
Value/range
Explanation
Default
value
PVStrT
Once the specified time
has elapsed, the inverter
switches from the operat-
ing state "Grid monitor-
ing" to the operating
state "Grid monitoring
time reached".
1 s to 300 s
‒
90 s
VArGra**
Gradient of reactive
power change
0%/s to 200%/s
‒
20%/s
QoDInvCurPv
***
Minimum allowed re-
verse current to PV array
−1,600 A to 0 A
‒
−60 A
MppFact
Ratio between maximum
power P
MPP
of the PV cell
at the maximum power
point and the product of
open-circuit voltage V
OC
and short-circuit current I
SC
0.5 to 1
‒
0.8
Serial Number
***
Inverter serial number
0 to 2147483647
‒
0
CntrySet*
Selection of valid power
frequency
Parameter can only be
changed in the operating
state "Stop".
J50
For 50 Hz grid
‒
J60
For 60 Hz grid
CardFunc*
MMC/SD memory card
function
ForcedWrite
Eject SD memory card
0
StoFailStt
Write fault memory to SD mem-
ory card
DtSet
Date:
20060101 to
20991231
yyyymmdd
0
TmSet
Time
0 to 235959
hhmmss
0
TmZn
Time zone
GMT ‒12:00 to
GMT 12:00
Configurable time zones
GMT 9:00
ExtSolIrrOfs
Offset of the external ir-
radiation sensor
−5,000 to 5,000
‒
0
ExtSolIrrGain
Amplification of external
irradiation sensor
−1,000 to 1,000
‒
1
14 Operating Data and Parameters
SMA Solar Technology AG
System Manual
MVPS22JP-SH-en-11
234