Name
Description
Value/range
Explanation
Default
value
ExlTrfErrEna
Activation of hermetic
protection of MV trans-
former
Off
Deactivated
On
On
Activated
* To view or change this parameter, you must enter the installer password.
** To change this parameter, you must enter the installer password.
*** You can only view this parameter.
14.2.2 Sunny Central String-Monitor Controller
Name
Description
Value/range
Explanation
Default
value
Serial Number
Display of serial number
‒
The value cannot be changed.
‒
Firmware
Firmware version of operation
control unit
0 to 255
‒
‒
Firmware2
Firmware version of digital signal
processor
0 to 255
‒
‒
Dt
Entry of current date
20060101 to
20991231
Entered in the format
YYYYMMDD
‒
Tm
Entry of current time
0 to 235959
Entered in the format
HHMMSS
‒
TolGr1*
Deviation of group 1 currents
from mean value
5% to 100%
Parameter exists for all six
groups.
13%
MoniTmGr1On
*
Start time for monitoring of
group 1
07:00 a.m. to
7:00 p.m.
Parameter exists for all six
groups.
10:00 a.m.
MoniTmGr1Off
*
End time for monitoring of
group 1
07:00 a.m. to
7:00 p.m.
Parameter exists for all six
groups.
3:00 p.m.
MoniTmGrAl-
lOn*
Start time for monitoring of all
groups
07:00 a.m. to
7:00 p.m.
‒
10:00 a.m.
MoniTmGrAl-
lOff*
End time for monitoring of all
groups
07:00 a.m. to
7:00 p.m.
‒
3:00 p.m.
MoniTmComO
n*
Start time for monitoring of all
groups
07:00 a.m. to
7:00 p.m.
‒
10:00 a.m.
MoniTmComOf
f*
End time for monitoring of all
groups
07:00 a.m. to
7:00 p.m.
‒
3:00 p.m.
Ackn
Acknowledge errors
quit
‒
‒
14 Operating Data and Parameters
SMA Solar Technology AG
System Manual
MVPS22JP-SH-en-11
236
Summary of Contents for 1000-1SC