AC Output
Transformer vector groups
Dy11y11 / YNd11d11
Displacement power factor cos φ
0.9 overexcited to 0.9 underexcited
* information based on inverter
Efficiency
Maximum efficiency
97.6 %
European weighted efficiency
97.4 %
General Data
Width x height x depth
6058 mm x 2591 mm x 2438 mm
Weight
< 14 t
Operating temperature range
−25°C to +40°C / −25°C to +55°C*
Self-consumption in operation**
< 3800 W
Standby consumption***
< 200 W + 1200 W
Internal auxiliary supply voltage
230 V / 400 V (3/N/PE), 50 Hz / 60 Hz
Maximum permissible value for relative humidity (non-
condensing)
15% to 95%
Maximum operating altitude above mean sea level
1000 m
Maximum operating altitude above MSL for option "In-
stallation at high altitudes"
1001 m to 2000 m / 2001 m to 3000 m
Fresh air consumption**
6000 m
3
/h
Degree of protection of medium-voltage compartment as
per IEC 60529
IP23D
Degree of protection of transformer compartment and in-
verter compartment as per IEC 60529
IP00
* optional
** information based on inverter
*** separated according to consumption of the inverter and standby power losses of the transformer
15 Technical Data
SMA Solar Technology AG
System Manual
MVPS22JP-SH-en-11
248