Attaching the Support Feet to the MV Power Station
The MV Power Station must be installed on the support surface with six support feet. The support feet for the station
container can be found in the accessories kit in the medium-voltage switchgear compartment. The four outer support
feet can be attached to the MV Power Station using the T-head bolts. The center support feet must be tightened. The
height of the standard support feet is adjustable (if necessary). After the mounting process of the MV Power Station is
completed, the height of the standard support feet can no longer be adjusted.
Requirement:
☐ To attach the support feet to the MV Power Station, you must place the station on temporary platforms (e.g. crane
support plates). The platforms must be at least 450 mm high.
Figure 25: Attachment of the support feet during unloading of the MV Power Station at the mounting location
Required mounting material (included in the scope of delivery):
☐ Six support feet for the MV Power Station