2. Tighten the nut of the T-head bolt (width across flats: 36 mm).
3. Repeat steps 1 and 2 for each support foot with T-head bolt.
4. Align the stud bolt of the support foot for the side of the
container outwards, guide it into the middle fitting of the station
container and mount it with the nut (width across flats: 30 mm).
5. Mount the second middle support foot as described in step 4.
6. Adjust the height of the support feet using the bottom nuts
(width across flats: 36 mm). The height of the support foot must
be at least 350 mm. Align the support foot so that the base
plate is flush with the MV Power Station.
7. Set the height of the support feet of the MV Power Station so that the device is horizontal and its weight is equally
distributed over all support feet.
4.7
Mounting the MV Power Station
The MV Power Station can be mounted and anchored on flagstones, pile-driven steel pillars, strip foundations,
concrete slabs or concrete pillars (see "Information on Transport and Installation of the MV Power Station"). The
customer is responsible for mounting and anchoring the MV Power Station on the support surface. Which foundation
option is selected is at the discretion of the customer. If the mounting location is subject to strong winds, the support feet
should be anchored to the foundation.
For the option "Seismic and Storm Qualification", stricter requirements apply to the foundations. The MV Power Station
comes with special support feet, which need to be integrated into the concrete foundation. Furthermore, the protection
roofs for the inverter compartment and transformer compartment must be removed. For further information on the
installation for the option "Seismic and storm qualification," consult the transport and installation conditions.
The cooling concept of the MV Power Station uses the service platforms to dissipate the warm exhaust air. For this
reason, the MV Power Station must be operated with open service platforms. To enable this, support feet must be
attached to the service platforms. The support feet for the service platforms can be found in the accessory kit in the
medium-voltage switchgear compartment. Mounting of the service platforms is the responsibility of the customer.
Mounting of the service platforms must be completed prior to commissioning.
Hand rails for the service platforms of the MV Power Station
The service platforms are provided by SMA Solar Technology AG.
Local regulations for hand rails must be observed. Hand rails for the service platforms are not included in the
scope of delivery of the MV Power Station and must be provided on-site.
4 Transport and Mounting
SMA Solar Technology AG
System Manual
45
MVPS22JP-SH-en-11
Summary of Contents for 1000-1SC