Procedure:
1. Switch the inverter to
Stop
.
2. Connect the supply voltage (see Section 7.9.1, page 103).
☑ The fans start to run for a few moments.
✖ The fans do not start up?
• Contact Service partner.
6.6.2
Checking the Heating Elements and Hygrostat
Figure 37: Position of the heating element and the hygrostat
Position
Designation
A
Hygrostat
B
Heating element
Danger to life due to electric shock or electric arc if live components are touched
If the MV Power Station and its devices are not correctly disconnected, dangerous voltages may be present in the
components which, if touched, will result in death or serious injury.
• Disconnect the MV Power Station (see Section 7.6, page 101).
• After switching off the inverter, wait at least 15 minutes before opening it to allow the capacitors to discharge
completely.
• Ensure that the MV Power Station and its devices are voltage-free.
6 Commissioning
SMA Solar Technology AG
System Manual
MVPS22JP-SH-en-11
94