11 Troubleshooting
SMA America, LLC
68
SB3-5TLUS22-IA-en-12
Installation Manual
7305
Update RS485I
module failed
Internal device fault, the inverter continues
feeding power into the grid.
Corrective measures:
• Re-try update.
• If this error occurs again, contact the
SMA Service Line.
7311
Update language table
failed
Internal device fault, the inverter continues
feeding power into the grid.
Corrective measures:
• Re-try update.
• If this error occurs again, contact the
SMA Service Line.
7316
Update Speedwire
module failed
Internal device fault, the inverter continues
feeding power into the grid.
Corrective measures:
• Re-try update.
• If this error occurs again, contact the
SMA Service Line.
7326
Webconnect update
unsuccessful
Internal device fault, the inverter continues
feeding power into the grid.
Corrective measures:
• Re-try update.
• If this error occurs again, contact the
SMA Service Line.
7335
Zigbee update failed
Internal device fault, the inverter continues
feeding power into the grid.
Corrective measures:
• Re-try update.
• If this error occurs again, contact the
SMA Service Line.
7508
External fan fault
The fan is contaminated or defective. The inverter
may reduce its power due to overheating. The
inverter continues feeding power into the grid.
Corrective measures:
• Clean the fan
• Replace the fan.
Event number
Display message
Cause and corrective measures