11 Troubleshooting
SMA America, LLC
70
SB3-5TLUS22-IA-en-12
Installation Manual
8801 to 8803
No display
This error message can have 3 causes but the
inverter continues to feed into the utility grid.
The ambient temperature is lower than ‒13°F
(‒25°C). The display switched off for protection.
The inverter cannot identify the display type.
No display is connected to the inverter or the
connection is defective.
Corrective measures:
• If the display switched off due to the ambient
temperature being too low, wait until the
ambient temperature is above ‒13°F
(‒25°C).
• If the ambient temperature is above ‒13°F
(‒25°C), contact the SMA Service Line.
9002
Grid guard code
invalid
The SMA Grid Guard code entered is incorrect.
The parameters are still protected and cannot be
changed.
Corrective measures:
• Enter the correct SMA Grid Guard code.
9003
Grid param. locked
The parameters are now locked. The parameters
cannot be changed.
Corrective measures:
• Unlock the parameters with the
SMA Grid Guard code.
Event number
Display message
Cause and corrective measures