SMA Solar Technology AG
Parameter Lists
Technical Description
SBU2200-TEN083320
143
221
04
BatTmpMax
degC
40
maximum battery temperature
221
05
BatTmpStr
degC
35
battery restart temperature following stop
due to overtemperature
222# Bat Chargemode
222
01
BatChrgCurMax
A
80
battery charging current limit (depends on
nominal battery capacity), 60 % of the
nominal battery capacity (221#02)
222
02
AptTmBoost
min
120
absorption time for normal charge
120 = VRLA
90 = FLA
300 = NiCd
depending on the setting in QCG
222
03
AptTmFul
h
5
absorption time for full charge
5 = VRLA
5 = FLA
7 = NiCd
depending on the setting in QCG
222
04
AptTmEqu
h
10
absorption time for equalization charge
10 = VRLA
10 = FLA
10 = NiCd
depending on the setting in QCG
222
05
CycTmFul
d
14
full charge cycle time
222
06
CycTmEqu
d
180
equalization charge cycle time
222
07
ChrgVtgBoost
V
2.4
cell voltage nominal value for normal
charge
2.4 = VRLA
2.55 = FLA
1.65 = NiCd
depending on the setting in QCG
222
08
ChrgVtgFul
V
2.4
cell voltage nominal value for full charge
2.4 = VRLA
2.5 = FLA
1.65 = NiCd
depending on the setting in QCG
222
09
ChrgVtgEqu
V
2.4
cell voltage nominal value for equalization
charge
2.4 = VRLA
2.5 = FLA
1.65 = NiCd
depending on the setting in QCG
Menu
no.
Parame
ter no.
Parameter name
Range/unit
Default
value
Description