Parameter Lists
SMA Solar Technology AG
146
SBU2200-TEN083320
Technical Description
240# Set Relay
Menu
no.
Parame
ter no.
Parameter name
Range/unit
Default
value
Description
241# Relay General
241
01
Rly1Op
Off
On
AutoGn
AutoLodExt
AutoLod1Soc
AutoLod2Soc
Tmr1
Tmr2
AptPhs
GnRn
ExtVfOk
GdOn
Error
Warm
Run
Ens1
Ens2
BatFan
AcdCir
AutoGn
function of relay 1:
= switched off
= switched on
= automatic generator connection
= automatic load disconnection, only
activated if external sources are present
= automatic connection / disconnection of
loads due to SOC1
= automatic connection / disconnection of
loads due to SOC2
= programmable timer 1
= programmable timer 1
= absorption phase is active
= generator is running
= ext. voltage and frequency in permissible
range
= ext. grid is connected
= error
= warmup
= operation
(= currently has no function)
(= currently has no function)
= battery room fan
= electrolyte pump
241
02
Rly2Op
see 241.01
AutoLodExt
function of relay 2:
for details, see 241.01
242# Relay Load
242
01
Lod1SocTm1Str
%
30
SOC limit for load shedding 1 start for t1
242
02
Lod1SocTm1Stp
%
50
SOC limit for load shedding 1 stop for t1
242
03
Lod1SocTm2Str
%
30
SOC limit for load shedding 1 start for t2
242
04
Lod1SocTm2Stp
%
50
SOC limit for load shedding 1 stop for t2
242
05
Lod1Tm1Str
hhmmss
0
load shedding 1 time 1
(begin time 1, end time 2)
242
06
Lod1Tm2Str
hhmmss
0
load shedding 1 time 2
(begin time 2, end time 1)
242
07
Lod2SocTm1Str
%
30
SOC limit for load shedding 2 start for t1
242
08
Lod2SocTm1Stp
%
50
SOC limit for load shedding 2 stop
for t1