SMA Solar Technology America LLC
6 Electrical Connection
Installation Manual
CU1000-US-11-IA-en-13
31
6.5 Connecting the PV Array
Cable requirements:
☐ The DC cables of the PV array must be designed in accordance with the installation
requirements applicable on site and for temperatures of +194°F (+90°C).
☐ The maximum cable length, which is dependent on the conductor cross-section, must be
adhered to.
☐ Cable type: copper wire
☐ Conductor cross-section: 14 to 6 AWG
Requirements:
☐ The conduits must be correctly connected to the Connection Unit (see Section 6.3).
☐ The DC switch-disconnector must be switched
OFF
and the lid must be dismantled.
Procedure:
Connect the DC cables of the PV array to INPUT A and B as follows:
3. Lead the DC cables of the PV array into the interior of the Connection Unit.
4. Strip the insulation of all cables by
3
⁄
8
in (9 mm).
1.
Danger to life due to electric shock
• Make sure that all devices (e.g. inverter) connected to the Connection Unit are switched
off and protected against reconnection (see manual of the respective device).
• Cover the PV modules.
2.
Danger to life due to electric shock
The strings in the Connection Unit are combined to two output circuits (A and B). If there is
reverse polarity of a PV string, there can be short-circuit current flowing when string fuses are
inserted, string fuse holders are closed, and the DC switch-disconnector is open.
• Open all string fuse holders.