4.3.5.3
Concrete pillar
Minimum lengths of the concrete pillars
The below-ground depth of the concrete pillars must satisfy the structural requirements.
The concrete pillars must have the following properties:
☐ The concrete pillars must be suitable for the weight of the product.
☐ The concrete pillars must be mounted on solid ground.
☐ The concrete pillars should have the following minimum dimensions:
750 mm
500 mm
500 mm
Figure 16: Dimensions of the concrete pillars (example)
A
B
A
C
A
A
A
B
SMA
Figure 17: Concrete pillars (example)
Position
Designation
A
Concrete pillar
B
Solid ground, e.g. gravel
C
Pea gravel ground
4.3.5.4
Strip foundations
The strip foundations must have the following properties:
☐ The strip foundations must be suitable for the weight of the product.
☐ The strip foundations must extend at least down to the frost line.
☐ Each strip foundation must have the following width: 500 mm to 600 mm.
☐ The depth of the strip foundation must be at least 200 mm greater on each side than the depth of the container.
4 Information for Installation
SMA Solar Technology AG
Transportation and Installation Requirements
MVPS22JP-TA-en-20
24