Recesses for the MV Power Station with two Inverters
Figure 23: Position and recommended dimensions of recesses with recommended foundation area
Position
Designation
A
Recess underneath the inverter for insertion of the following cables:
• DC cable
• Cable for analog setpoint
• Connecting the cable for remote shutdown
• Cable for external insulation monitoring
B
Recess underneath the medium-voltage switchgear for insertion of the AC cables:
• Maximum six cables per cable panel; maximum cable diameter: 55 mm
C
Recess underneath the Communit for insertion of the data cables and grounding cables:
• 3 x PG9 for cable diameters from 6 mm to 8 mm
• 3 x PG11 for cable diameters from 8 mm to 10.5 mm
• 4 x PG16 for cable diameters from 13 mm to 16 mm
• 4 x PG21 for cable diameters from 17 mm to 20 mm
D
Recess underneath the transformer compartment:
• Oil spill containment
E
Inspection shaft for oil drain valve
4 Information for Installation
SMA Solar Technology AG
Transportation and Installation Requirements
MVPS22JP-TA-en-20