Oil drain valve (2'')
F
Grounding bolt of the oil spill containment (diameter: 8 mm)
Oil Spill Containment Dimensions and Weight
Width
Height
Depth
Weight
1620 mm
> 320 mm*
2400 mm
100 kg
* The height of the oil spill containment can be adjusted.
4.4.2
Oil Spill Containment for the MV Power Station with Two Inverters
The oil spill containment must be recessed in the foundation and must be positioned underneath the transformer
compartment. There must be enough space in the foundation for the inspection shaft. The support surface around the
oil spill containment should be pea gravel ground. The oil spill containment should be fitted with theft protection.
The inspection shaft is to be installed on-site.
Space for maintenance work must be provided
For the order option with oil spill containment, ensure there is sufficient space available for the oil spill containment
and any necessary maintenance work.
Figure 26: Oil spill containment for the MV Power Station with two inverters
Position
Designation
A
Inverter
B
Transformer compartment
C
Medium-voltage switchgear
D
Oil spill containment with four oil separators
E
Oil drain valve (2'')
4 Information for Installation
SMA Solar Technology AG
Transportation and Installation Requirements
MVPS22JP-TA-en-20
32