6 Technical Data
6.1 Technical
Data
Parameter
MLX 60
AC
Rated apparent power
1)
60 kVA
Rated active power
2)
60 kW
Reactive power range
1)
0–60 kVAr
Rated grid voltage (voltage range)
3P + PE (delta or WYE) / 400-480 V (+/- 10%)
Grounding schemes supported
TT, TN
Rated current AC
3 x 87 A
Max. current AC
3 x 87 A
AC current distortion (THD at nominal output power)
< 1%
Power factor default
> 0.99 at rated power
Power factor - regulated
0.8 over-excited, 0.8 under-excited
Stand-by power consumption (comm. only)
3 W
Rated grid frequency (frequency range)
50/60 Hz (+/- 10%)
DC
Input voltage range
565–1000 V @ 400 V
ac
680–1000 V @ 480 V
ac
Rated voltage DC
630 V @ 400 V
ac
710 V @ 480 V
ac
MPPT voltage range - rated power
570–800 V @ 400 V
ac
685–800 V @ 480 V
ac
Max. voltage DC
1000 V
Min. on grid power
100 W
Max. MPPT current DC
4)
110 A
Max. short-circuit current DC
4)
150 A
MPP tracker/Input per MPPT
1 / 1 (external string combining)
Efficiency
Max. efficiency EU/CEC
98.8%
EU efficiency at 570 V
dc
98.5%
CEC efficiency at 400/480 V
ac
98.0% / 98.5%
MPPT efficiency static
99.9%
Enclosure
Dimensions (H x W x D)
740 × 570 × 300 mm (29 × 22.5 × 12 in)
Weight
75 kg (165 lbs)
3)
Acoustic noise level
55 dB(A) (preliminary value)
Table 6.1 Specifications
1)
At rated grid voltage.
2)
At rated grid voltage, Cos(phi)=1.
3)
Depending on installed options.
4)
Under any conditions.
Technical Data
28
L00410648-02_02 / Rev. date: 2014-10-03
6
6