International standards
MLX series
Utility characteristics
IEC 61727
EN 50160
IEEE 1547 UI
Table 6.3 International Standards Compliance
Approvals and certificates are available from the download
area at
www.sma.de
.
6.4 Mains Circuit Specifications
Parameter
Specification
Maximum inverter current, I
acmax
87 A
Recommended blow fuse type gL/gG (IEC
60269-1)
100-125 A
Recommended blow fuse Class T (UL/USA)
125 A
Recommended MCB type B or C
125 A
Maximum fuse size
125 A
Table 6.4 Mains Circuit Specifications
NOTICE
Observe local regulations.
6.5 Auxiliary
Interface
Specifications
Interface
Parameter
Parameter Details
Specification
Ethernet
Cable
Cable jacket diameter (
⌀
)
2 x 5-7 mm
Cable type
Shielded Twisted Pair (STP CAT 5e or
SFTP CAT 5e)
1)
Cable characteristic impedance
100
Ω
– 120
Ω
RJ-45 connectors:
2 pcs RJ-45 for Ethernet
Wire gauge
24-26 AWG (depending on mating
metallic RJ-45 plug)
Cable shield termination
Via metallic RJ-45 plug
Galvanic interface insulation
Yes, 500 Vrms
Direct contact protection
Double/Reinforced insulation
Yes
Short-circuit protection
Yes
Communication
Network topology
Star and daisy chain
Cable
Max. cable length between
inverters
100 m (328 ft)
Max. number of inverters
Per Inverter Manager
42
Table 6.5 Auxiliary Interface Specifications
1)
For outdoor and/or burial use, ensure that the appropriate type of
Ethernet cable is used.
Illustration 6.1 Auxiliary Interfaces (Cutout of Inverter Installation Compartment)
Technical Data
30
L00410648-02_02 / Rev. date: 2014-10-03
6