Sunny Boy 2500U
Installation and Operator’s Manual
SB2500U-11:NE
-
30
-
SMA Regelsysteme GmbH
4.2 Ground Fault Indicator
Isolation failure
Green LED off
Red LED on
Yellow LED on
This is the result of a ground fault of the PV panel. The inverter then has to indicate this
condition and disconnect from the grid. The inverter has to be reset manually, it cannot
restart automatically.
CAUTION:
The PV-array must be inspected for ground faults.
Please have a look at chapter 3 “First switching on”.
If the ground fault of the PV panel is removed, the inverter switches from “permanent de-
vice disable” to “GFDI Fuse open” failure and the yellow LED is off.
The red LED is still on. Now the following must be done:
Defective GFDI fuse
Green LED off
Red LED on
Yellow LED off
The failure “GFDI Fuse open” is displayed. If an intact fuse is then installed, the inverter
restarts operation. The “GFDI Fuse open” failure persists in case the fuse is defective.
WARNING
: For continued protection against risk of fire replace only with
same types and rating of fuse. The type is Littelfuse KLKD 1 AMP 600 V
AC / DC.