6 Electrical Connection
SMA Solar Technology AG
Operating manual
NA-BOX-12-3-20-BE-en-12
18
6
Electrical Connection
6.1
Overview of the Connection Area
6.1.1
Interior View
A
C
H
D
E
G
F
B
Figure 7: Overview of the connection area
Position
Designation
A
Terminal
X210, X211
with spring-cage terminals to connect the control cables
B
De-energized surge arrester
C
Terminal
X201:7-9
with spring-cage terminals
L1
,
L2
and
L3
to connect the line con-
ductors of the Multicluster-Box
D
Terminal
X201:6
with spring-cage terminals
PE
to connect the grounding conductor of
the Multicluster-Box
E
Terminal
X201:10
with spring-cage terminals
N
to connect the neutral conductor of
the Multicluster-Box
F
Terminal
X201:4
with spring-cage terminals
N
to connect the neutral conductor of the
utility grid
G
Terminal
X201:5
with spring-cage terminals
PE
to connect the grounding conductor of
the utility grid
H
Terminal
X201:1-3
with spring-cage terminals
L1
,
L2
and
L3
to connect the line con-
ductors of the utility grid