6 Disassembling the defective CON assembly
SMA Solar Technology AG
Replacement Manual
CON-SMC46-60A-70HV-RM-xx-10
14
11. Ensure that no voltage is present between L and PE at the AC terminal using a suitable
measuring device.
12. Actively discharge the DC link. For this purpose use,
for example, a 2-pole voltage detector that does not
have its own voltage source. Using the voltage
detector, conduct a measurement on the connection
screws of the terminal of the DC link connection
cable on the CON assembly until a value of 0 V is
displayed.
13.
NOTICE
Damage to the inverter due to electrostatic discharge
The internal components of the inverter can be irreparably damaged by electrostatic
discharge.
• Ground yourself before touching any component.
6
Disassembling the defective CON assembly
A
C
D
F
B
E
G
Figure 2 : Overview of the CON assembly
Procedure:
1. Disconnect the inverter from all voltage sources (see Section 5, page 13).
2. Remove the ribbon cable (B) from the CON assembly, the OCS assembly and the power
assembly (AST).
ENGLISH
Summary of Contents for NR-SMC-CON