Displays and Messages
6-6
SMA America
SB1100U-11:SE1604
Fault Indicators
Ground Fault
The inverter has detected a ground fault in the PV system and has disconnected from the
grid.
The ground fault must be located and cleared and the inverter reset manually.
(The inverter will not restart automatically)
Defective GFDI Fuse
The GFDI fuse located in the fuse holder on the bottom of the inverter is defective. If the
fuse has blown due to a ground fault, the fault must be cleared before replacing the fuse.
CAUTION: For continued protection against the risk of fire,
replace the GFDI fuse with fuses of the same type and rating
only. The recommended type is a
Littelfuse KLKD 1 Amp, 600V
AC/DC