Displays and Messages
SB1100U-11:SE1604
SMA America
6-9
High Grid Impedance
The yellow LED is on for 5 seconds, remains off for 3 seconds and then blinks 3 times.
The code is repeated 3 times. If the condition remains the code will continue to be sent.
The inverter has detected a grid impedance value that is too high for safe operation.
If this condition occurrs often, the actual grid impedance can be checked using the
Sunny Boy Control or Sunny Data. High grid impedance can often be avoided or
corrected by increasing the diameter of the AC cables between the grid connection and
the inverter.