Displays and Messages
SB1100U-11:SE1604
SMA America
6-15
Messages of the Sunny Display in Case of a Failure
In case of a failure the Sunny Display switches to „Failure“ and the background
illumination is activated.
The upper line indicates one of the three following failure types:
• Disturbance
A condition is only considered as a Disturbance as long as the reasons for this con-
dition still are present.
• Error
A condition is considered as an Error in case the inverter cannot restart without user
interaction.
The bottom line indicates the type of a failure for 5
seconds.
Failures that result from a specific value that e.g. exceeds
a limiting are specified with the value that caused the
failure as well as the current value.
The normal operating data is displayed after 5 seconds.
The display starts from the beginning again in case the
failure is still present. For detailed information concerning
the failure messages have a look to "Measuring Channels
and Messages" (page 6-18).
„Error ROM“ indicates that the Sunny Boy has detected a
defective firmware in the EEPROM. Contact SMA in order
to remove this failure.
Indication of a failure
and failure type
Disturbance
Fac-Bfr
Display of the value that caused the
failure and the current value
at:
59.31Hz
present:
59,30Hz
Indication of defective fimware
Error
ROM
Summary of Contents for SB1100U
Page 1: ...Photovoltaic Grid Tied String Inverter Sunny Boy 1100U Installation Guide SOLARTECHNOLOGY...
Page 2: ......
Page 8: ...vi SMA America SB1100U 11 SE1604...
Page 12: ...Unpacking and Inspection 2 2 SMA America SB1100U 11 SE1604...
Page 44: ...Commissioning the Sunny Boy 5 6 SMA America SB1100U 11 SE1604...
Page 68: ...Displays and Messages 6 24 SMA America SB1100U 11 SE1604...
Page 72: ...Troubleshooting 7 4 SMA America SB1100U 11 SE1604...
Page 74: ......
Page 75: ......
Page 76: ......