Displays and Messages
6-22
SMA America
SB1100U-11:SE1604
Sunny Boy 1100U Operating Parameters
CAUTION: Any unauthorized modifications of the operating
parameters can
• Result in serious injuries or casualties due to altered internal safety
precautions within the Sunny Boy
• Void the UL Listing of the Sunny Boy
• Void the warranty of the Sunny Boy
• Could void any utility interconnection agreement
Never change the operating parameters without explicit permission and
instructions!
Table 6-1 Operating Parameters of the Sunny Boy 1100U (changeable)
Name
Unit
Range
Default
Description
E-Total
E-total
kWh
0 ... 200000
Total energy yield (E_Total) and total operating
hours (h_Total) of the inverter. Changing the value
can be necessary when a Sunny Boy is exchanged
and you wish to match the previously acquired
data. These parameters can only be changed after
entering the installers password.
h-Total
h-total
h
0 ... 200000
Vconst-Setval
V
150 ... 430
410
PV Setpoint voltage for constant voltage operation.
These parameters only are important in case the
parameter „Operating Mode“ is set to „V-const“.
Vac-Min
V
180 ... 300
213
Lower (Vac-Min) and upper (Vac-Max) limit of
permissible AC voltage (anti-islanding).
These parameters can only be changed after
entering the installers password.
Vac-Max
V
180 ... 300
262
Fac-delta-
Hz
0 ... 4.5
0.69
Maximum frequency above (Fac-Delta+) and below
(Fac-Delta-) 60 Hz grid frequency before anti-
islanding trips. These parameters can only be
changed after entering the installers password.
Fac-delta+
Hz
0 ... 4.5
0.49
dFac-MAX
Hz/s
0.005 ... 4.0
0.5
Maximum „rate of change of frequency“ before
anti-islanding trips. This parameter can only be
changed after entering the installers password.
dZac-Max
mOhm
0 ... 20000
2000
Maximum „rate of change of grid impedance“
before anti-islanding trips.
Vpv-Start
V
150 ... 400
180
Voltage where the Sunny Boy starts connecting to
the grid.
T-Start
s
5 ... 1600
10 / 300
10 Seconds: The time the inverters waits to connect
to the grid when turned on.
300 Seconds: The time the inverter waits to
reconnect to the grid if a grid disturbance is
detected during normal operation.
Summary of Contents for SB1100U
Page 1: ...Photovoltaic Grid Tied String Inverter Sunny Boy 1100U Installation Guide SOLARTECHNOLOGY...
Page 2: ......
Page 8: ...vi SMA America SB1100U 11 SE1604...
Page 12: ...Unpacking and Inspection 2 2 SMA America SB1100U 11 SE1604...
Page 44: ...Commissioning the Sunny Boy 5 6 SMA America SB1100U 11 SE1604...
Page 68: ...Displays and Messages 6 24 SMA America SB1100U 11 SE1604...
Page 72: ...Troubleshooting 7 4 SMA America SB1100U 11 SE1604...
Page 74: ......
Page 75: ......
Page 76: ......