Wiring and Connecting the Sunny Boy
Wiring the AC Output
4-6
SMA America
SB1100U-11:SE1604
Percent voltage drop for 240 V AC service
Figure 4-3 Energy Losses in Various Wire Sizes and Wire Lengths
The Sunny Boy 1100U is designed to feed 213 V AC to 262 V AC to the utility grid at
frequencies from 59.3 Hz to 60.5 Hz. Table 4-1 lists the voltage and frequency limits
for the AC connection. See our web site for additional information.
Table 4-1 Voltage and Frequency Limits for the AC Connection
Connecting the AC Wires
Use the following procedure to connect the AC wires to the Sunny Boy:
WARNING: You must connect the wires that carry the AC
voltage from the Sunny Boy to the utility grid in the order
described in this procedure. Deviating from this procedure
could expose you to hazardous voltages that can cause
serious injury and/or death.
1. Turn OFF the main breaker in the main utility breaker box.
Voltage Range
213 V - 262V
Frequency Range
59.3 Hz - 60.5 Hz