3  Grid Failure

SMA Solar Technology AG

Technical Information

7

STP60-SHP75-10-Parameter-TI-en-12

2.6.2

Reconnection Time

If a fault on the grid makes the inverter disconnect and the grid then afterwards stabilizes within the allowed voltage
and frequency ranges, then the inverter is allowed to reconnect to the grid with this time delay. The reconnection time
is usually shorter than the connection time, but it can also be the same time or longer than the connection time.

Parameter name

Setting range

Step size

T_RECON

0 s to 1800 s

0.01 s

2.6.3

Short Interruption Time

The short interruption time is the permissible time period after which the inverter must start the complete reconnection
procedure. If the grid fault is remedied in a shorter time period, the inverter can reconnect to the utility grid after the
reconnection time 

T_RECON

.

Parameter name

Setting range

Step size

T_SHT_INT

0 s to 1800 s

0.01 s

2.6.4

Time to Alarm

Time to alarm is the period which the inverter must wait before generating an alarm event. This is to prevent the inverter
from generating alarm events all the time.

Parameter name

Setting range

Step size

T_ALARM

0 s to 1800 s

0.01 s

2.6.5

Voltage and Frequency Connection Limits

The minimum and maximum connection limits for voltage and frequency define the value range in which the inverter
can connect to the utility grid.

Parameter name

Setting range

Step size

UMIN_CON

UMIN1 to UNOM

0.1 V

UMAX_CON

UNOM to UMAX1

0.1 V

FMIN_CON

FMIN1 to FNOM

0.01 Hz

FMAX_CON

FNOM to FMAX1

0.01 Hz

2.6.6

Ramp-In

The ramp-in factor describes the ramp for the power up of the inverter. More details can be found in the settings for
grid management services under parameter 

Connection/reconnection ramp rate

.

3

Grid Failure

3.1

Active Frequency Shift

The active frequency shift works in the way that if the grid becomes unstable for any reason, this function then helps to
push the grid even more of balance so that the inverter disconnects due to RoCoF or one of the regular disconnection
parameters.

Parameter name

Setting options

LOM_F_SHF_K0/_K1

on (1)

off (0)

Summary of Contents for SHP 75-10

Page 1: ...2 F3 F4 Hom e Back OK F1 F2 F3 F4 Hom e Back OK STP60 SHP75 10 Parameter TI en 12 Version 1 2 ENGLISH Technical Information SUNNY TRIPOWER 60 SUNNY HIGHPOWER PEAK1 Description of the Operating Paramet...

Page 2: ...4 Settings of Grid Management Services Fault Ride Through FRT 9 5 Settings of Grid Management Services 12 5 1 Default Settings 13 5 1 1 Selecting the Control Modes for Reactive Power Provision 13 5 1...

Page 3: ...STP60 SHP75 10 Parameter TI en 12 5 3 6 PF U Power Factor as a Function of Grid Voltage 18 5 3 7 PF ext Power Factor as a Function of an External Setpoint 18 5 3 8 P V Active Power as a Function of Gr...

Page 4: ...minal Voltage This parameter refers to the nominal grid voltage of a country In most countries only one official grid voltage is valid For countries with several official grid voltages additional grid...

Page 5: ...the three key values is used in your file Parameter name Setting range Step size UMAX UNOM to 350 Vac L N 0 1 Vac L N T_UMAX 0 05 s to 90 0 s 0 01 s 2 4 Manual Restart With the function Manual Restar...

Page 6: ...e key values is used in your file Parameter name Setting range Step size FMIN 45 Hz to FNOM 0 01 Hz T_FMIN 0 05 s to 90 0 s 0 01 s 2 5 2 Disconnection due to Overfrequency The overfrequency disconnect...

Page 7: ...to alarm is the period which the inverter must wait before generating an alarm event This is to prevent the inverter from generating alarm events all the time Parameter name Setting range Step size T_...

Page 8: ...tails can be found in the settings for grid management services under parameter Connection reconnection ramp rate 3 3 Rate of Change of Frequency The parameter RoCoF or Rate of Change of Frequency mea...

Page 9: ...gs to grid management services it is stored in the inverter The FRT function is set to cope with voltage dips down to 0 UNOM without time limit This is confirmed in the FRT performance test which was...

Page 10: ...e compared with the average root mean square values before the fault The relevant time frame for the average voltage before the grid fault can be set via the parameter FRT_T_U_AVG default 10 minutes F...

Page 11: ...as the total current does not exceed the limit After fault clearance reactive current feed in stays active for a certain transition period This period can be set with the grid code parameter FRT_T_TR...

Page 12: ...1 to 10 0 1 FRT_DIDU_POS_HVRT 1 to 10 0 1 FRT_DIDU_NEG_LVRT 1 to 10 0 1 FRT_DIDU_NEG_HVRT 1 to 10 0 1 FRT_IQ_MODE 0 or 1 FRT_T_BLK 0 s to 10 s 0 01 s FRT_T_TRANS 0 s to 10 s 0 01 s FRT_T_U_AVG 0 s to...

Page 13: ...for Reactive Power Provision Reactive power references can either be given as a direct reference for reactive power Q or as an indirect reference via the power factor PF The references are based on th...

Page 14: ...ng option P_LIM_IF_Q 80 to 100 default 100 5 1 4 Nominal Apparent Power at Point of Common Coupling PCC All grid management services in the inverter are based on the nominal apparent power at the poin...

Page 15: ...onnection see Section 2 Grid Protection Settings page 4 Parameter name Setting option Explanation ReleaseToStart 0 Immediate disconnection 1 Connection when grid parameter is in the permissible range...

Page 16: ...dicates the setpoint for the power factor PF only available if control mode 9 has been selected in the parameter ModeSelect Parameter name Setting range Step size PF_ref 0 8 to 1 0 for overexcitation...

Page 17: ...espectively 5 3 1 Q U Reactive Power as a Function of Grid Voltage This control mode uses the grid voltage to generate a reference value for the reactive power so that the grid voltage can be controll...

Page 18: ...w the lock out threshold The threshold for activation must be larger than or equal to the threshold for deactivation If this control mode shall always be available set lock_in_PPF lock_out_PPF 90 only...

Page 19: ...ose of this time delay is to reach a lower sensitivity in terms of transient frequency changes and higher reliability when detecting grid failures The amount of generated active power is still sampled...

Page 20: ...c curves in the reference table contain equal co or dinates x y B Example of programming the FP_of_f characteristic curve when hysteresis is required e g as per BDEW Thus the two characteristic curves...