Connecting External Sources
SMA Solar Technology AG
120
SI5048-TEN093630
Technical Description
14.2.6 Grid Failure
A grid fault is characterized by the voltage or frequency being outside of the permissible limits
(see section 14.2.4 ”Grid Reconnection” (page 118)) or the main power grid being disconnected.
In this case, the time limits are relevant: Smaller deviations are permitted for longer than large
deviations (see section 14.2.1 ”Boundary Conditions” (page 118)).
In case of a grid fault/failure, the main power grid is disconnected and the inverter is started from
silent mode.
14.2.7 Failures
Reverse Power
If the defined reverse power ("232.09 GdRvPwr" parameter) is exceeded for the time
"232.10 GdRvTm", the grid is disconnected. After reverse power, connection is blocked for at least
"231.03 ExtLkTm".
Grid Failure
If a grid failure is detected (failure at the master phase), the grid is disconnected immediately.
Grid Phase Failure
The failure of a phase (e.g. broken fuse) on a slave device is treated as a phase failure. The slave
device then disconnects this phase. If the phase is detected as being available again, it is reconnected.
The phase failure on the master device is treated as a grid failure (see above).
Slave Device Failure
If a slave device fails, the system continues to operate using the remaining devices of the cluster.
Waking Up from the Silent Mode
If the Sunny Island is in silent mode when there is a public grid failure, there is a short grid
failure in the stand-alone grid (see section 13.4.5 ”Silent Mode” (page 98)).