Parameter lists
SMA Solar Technology AG
152
SI5048-TEN093630
Technical Description
19.2.3 External Settings (230#)
231# Ext General
232# Grid Control
Number Name
Description
Value
Description
Default
value
03
ExtLkTm
Lock time after reverse
power or relay
protection
0 min ...
60 min
20 min
06
ExtSrc
External source
PvOnly
PV only
PvOnly
Gen
Generator
Grid
Grid
GenGrid Generator / Grid
Number Name
Description
displayed
value
Description
Default
value
01
GdVtgMin
Minimum grid voltage
230 V / 50 Hz 184 V
220 V / 60 Hz 194 V
02
GdVtgMax
Maximum grid
voltage
230 V / 50 Hz 264.5 V
220 V / 60 Hz 242 V
03
GdCurNom
Gird nominal voltage
16 A
04
GdFrqNom
Grid nominal
frequency
230 V / 50 Hz 50 Hz
220 V / 60 Hz 60 Hz
05
GdFrqMin
Minimum grid
frequency
230 V / 50 Hz 47.5 Hz
220 V / 60 Hz 59.3 Hz
06
GdFrqMax
Maximum grid
frequency
230 V / 50 Hz 50.2 Hz
220 V / 60 Hz 60.5 Hz
07
GdVldTm
Minimum time
required for grid
(voltage and
frequency) to be
within permissible
range for connection
230 V / 50 Hz 30 sec
220 V / 60 Hz 300 sec
08
GdMod
Grid interface
GridCharge Charging on
the grid
GridCharge
GridFeed
Charging and
feedback on
the grid
Summary of Contents for SI 5048