Parameter lists
SMA Solar Technology AG
154
SI5048-TEN093630
Technical Description
233# Grid Start
46
FedInCurAt
Maximum AC
charging current
230 V / 50 Hz 16 A
220 V / 60 Hz 16 A
47
FedInCurRt
Maximum AC
charging current
48
FedInCtl
EctCur
EctCur
IntCur
49
GdSocEna
Activate the grid
request based on
SOC
Disable
Enable
Disable
Enable
Disable
50
GdPwrEna
Activate the grid
request based on
power
Disable
Enable
Disable
Enable
Disable
Number Name
Description
displayed
value
Description
Default
value
01
GdSocTm1Str
SOC limit for switching on
the grid for time 1
40 %
02
GdSocTm1Stp
SOC limit for switching off
the grid for time 1
80 %
03
GdSocTm2Str
SOC limit for switching on
the grid for time 2
40 %
04
GdSocTm2Stp
SOC limit for switching off
the grid for time 2
80 %
05
GdTm1Str
Time 1 for grid request in
hh:mm:ss
Begin time 1, end time 2
06
GdTm2Str
Time 2 for grid request in
hh:mm:ss
Begin time 2, end time 1
07
GdPwrStr
Grid request starting
capacity
4 kW
08
GdPwrStp
Grid request
disconnection power limit
2 kW
Number Name
Description
displayed
value
Description
Default
value
Summary of Contents for SI 5048