SMA Solar Technology AG
Parameter lists
Technical Description
SI5048-TEN093630
159
237# CHP Start
Number Name
Description
displayed
value
Description
Default
value
01
ChpSocTm1Str
SOC limit for switching
on CHP plant for time 1
40 %
02
ChpSocTm1Stp SOC limit for switching
off CHP plant for time 1
80 %
03
ChpSocTm2Str
SOC limit for switching
on CHP plant for time 2
40 %
04
ChpSocTm2Stp SOC limit for switching
off CHP plant for time 2
80 %
05
ChpTm1Str
Time 1 for CHP plant
request in hh:mm:ss
Begin: Time 1,
End: Time 2
06
ChpTm2Str
Time 2 for CHP plant
request in hh:mm:ss
Begin: Time 2,
End: Time 1
07
ChpPwrEna
Activate CHP plant
request based on
power
Disable
Enable
Enable
Enable
Disable
08
ChpPwrStr
Generator request
switch-on power limit
4 kW
09
ChpPwrStrDly
Time delay for power
request for CHP plant
5 min
10
ChpManStr
Auto
Start
Stop
11
ChpAddOnTm
Time for the additional
CHP request activated
60 sec
12
ChpAddOffTm
Time for the additional
CHP request
deactivated
120 sec
13
ChpAddSocDel Distance to the next
SOC limit
5 %
Summary of Contents for SI 5048
Page 2: ......
Page 10: ...Table of Contents SMA Solar Technology AG 10 SI5048 TEN093630 Technical Description...
Page 43: ...SMA Solar Technology AG Electrical Connection Technical Description SI5048 TEN093630 43...
Page 209: ......
Page 210: ......
Page 212: ...4 4PMBS 5FDIOPMPHZ XXX 4 EF...