Troubleshooting
SMA Solar Technology AG
186
SI5048-TEN093630
Technical Description
20.5 Display of Errors and Events
Each error and each event have a unique three-digit display number that is created according to the
parameter/measuring value assignment. The events and errors have the identical numerical range:
• 1xx - INV - Inverter
• 2xx - BAT - Battery
• 3xx - EXT - Extern
• 4xx - GEN - Generator
• 5xx - GRD - Grid
• 6xx - RLY - Relay
• 7xx - SYS - System
• 8xx - AUX - external devices and components
20.6 Events
The meanings of the events displayed by the Sunny Island are described in the following table:
20.6.1 Category INV
Meaning of the abbreviations
"F" marks an error, "W" marks a warning and "E" marks an event.
In the event of an error, and provided it is recorded, "!" is displayed for an error that has
occurred and "C" is displayed for an error that has stopped.
Display no.
Description
E101
Wait status
E102
Startup process
E103
Operation
E104
operating on the generator (at external input)
E105
operating on the grid (at external input)
E106
Feed-in grid operation (at external input)
E107
Sleep mode (slave in single-phase systems)
E108
Silent mode on the grid
E110
Shutting down due to fault
E115
emergency charge
E118
Automatic start
E119
Manual start (transfer from standby mode into operation)
E120
Manual Stop (transition from operation to standby)
E129
External start (remote)
E130
External stop (remote)