Electrical Connection
SMA Solar Technology AG
48
SI5048-TEN093630
Technical Description
6.4.6 DigIn Digital Input
These terminals are used as a digital input for external electrical sources. For example, the feedback
contact for the GenMan (GenRn) is connected here.
For connection, proceed as follows:
1. Poke through the appropriate place in the cable insert with a pointed object.
2. Starting from the outside, feed the cable with cable end sleeves through the hole in the
Sunny Island.
3. Connect the cables correspondingly to the "DigIn" connection of the 4-pole print terminal
included in the delivery.
4. Tighten the terminals.
5. Insert the 4-pole print terminal into the "DigIn" socket on the Sunny Island.
Related Functions
If you connect a GenMan, or operate the system with the generator and grid (GenGrid)
in parallel, use the relays on the master device in order to activate the respective functions.
Further information
For more information on connecting and operating the GenMan, see the technical
description of the GenMan.