Initial Commissioning
Technical Description
SI5048-TEN093630
57
– External power supply unit (PvOnly, Gen, Grid, GenGrid)
GenGrid:
– Maximum generator current (0 to 224 A), default setting is "16 A"
– Generator interface (Manual, GenMan, Autostart), default setting is "Autostart"
– Maximum grid current (0 to 224 A), preset to "16 A"
Grid:
– Maximum grid current (0 to 224 A), preset to "16 A"
4. The following parameters must be set when
"New Battery"
is selected:
– Battery type (VRLA, FLA, NiCd), default setting is "VRLA"
– Nominal battery capacity (100 Ah - 10000 Ah), default setting: "100 Ah"
☑ After entering all parameters the following
notice appears.
5. Press <ENTER> to confirm.
☑ The notifications shown here are issued.
6. Press <ENTER> until you hear a peep.
☑ The Sunny Island has started and is in operation.
Adjustable parameters
For more information on adjustable parameters, see section 19 ”Parameter lists”
(page 137).
Note that some parameters can only be changed after entering the installer password
(see chapter 10.5 ”Entering the installer password” (page 73)), or in standby mode
(see section 9.2 ”Stopping the Sunny Island (Standby)” (page 61)).